features and benefits
The M-7011/M-7011D features current and voltage input as well as thermocouple input.
The module provides 1-channel analog input, 1-channel digital input that functions as a 50 Hz event counter, and 2-channel digital output that can be used as a high/low alarm.
The module also features open wire detection for the thermocouple input, and 3000 VDC intra-module isolation.
The M-7011(D) supports Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7011(D).
- 1 Analog Input
- Current, Voltage, and Thermocouple Inputs
- Open Thermocouple Detection
- High Resolution: 16-bit
- 50 Hz Event Counter for Digital Input
- High/Low Alarm for Digital Output
- Built-in Dual Watchdog
specifications
CPU ModuleWatchdog Timer | Module, Communication (Programmable) |
---|
DisplayType | 5-Digit 7 Segment LED Display |
---|
IsolationIntra-module Isolation | 3000 VDC |
---|
EMS ProtectionEFT (IEC 61000-4-4) | ±4 kV for Power Line |
---|
ESD (IEC 61000-4-2) | ±2 kV Contact for Each Terminal |
---|
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
---|
LED IndicatorsStatus | 1 x Power and Communication |
---|
Analog InputChannels | 1 Differential |
---|
Type | Voltage | Current | Thermocouple |
---|
Sensor Type | Thermocouple: J, K, T, E, R, S, B, N, C |
---|
Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V | Current: ±20 mA (requires optional external 125 Ω resistor) |
---|
Resolution | 16-bit |
---|
Accuracy | ±0.1% of FSR |
---|
Sampling Rate | 10 Hz (Total) |
---|
Input Impedance | > 400 kΩ |
---|
Common Voltage Protection | ±5 VDC |
---|
Overvoltage Protection | ±5 VDC |
---|
Open Wire Detection | For Thermocouple Only |
---|
Digital Input/CounterChannels | 1 |
---|
Type | Dry Contact |
---|
Sink/Source (NPN/PNP) | Source |
---|
ON Voltage Level | Close to GND |
---|
OFF Voltage Level | Open |
---|
Input Impedance | 3 kΩ |
---|
Overvoltage Protection | ±30 VDC |
---|
Digital OutputChannels | 2 |
---|
Type | Open Collector |
---|
Sink/Source (NPN/PNP) | Sink |
---|
Load Voltage | +3.5 ~ +30 VDC |
---|
Load Current | 30 mA/Channel |
---|
Power on Value | Programmable |
---|
Safe Value | Programmable |
---|
COM PortsPorts | 1 x RS-485 |
---|
Baud Rate | 1200 ~ 115200 bps |
---|
Data Format | (N, 8, 1) |
---|
Protocol | Modbus RTU, DCON |
---|
PowerReverse Polarity Protection | Yes |
---|
Input Range | +10 ~ +30 VDC |
---|
Consumption | 1.5 W |
---|
MechanicalDimensions (mm) | 72 x 123 x 35 (W x L x H) |
---|
Installation | DIN-Rail Mounting |
---|
EnvironmentOperating Temperature | -25 ~ +75 °C |
---|
Storage Temperature | -40 ~ +85 °C |
---|
Humidity | 10 ~ 95% RH, Non-condensing |
---|