The I-97024U and I-97028U are source type analog output modules, which offer 4 and 8 single-ended analog output channels. Every channel can be programmed to an individual output range of 0 ~ 5 V, ±5 V, 0 ~ 10 V, ±10 V, +4 ~ +20 mA or 0 ~ +20 mA. Open wire detection is provided for +4 ~ +20 mA output. Options for configuring power-on and safe values are also included.
The I-97024U and I-97028U provide RF immunity level matching that defined by IEC 61000-4-3 standard, together with 4 kV ESD protection as well as 3000 VDC intra-module isolation
I-97028U CR: 8-channel 16-bit Isolated Source Type Voltage or Current Output Module (RoHS)

  • 4/8-channel Voltage or Current Output
  • Individual Channel Configuration
  • 3000 VDC Intra-module Isolation
  • Open Wire Detection for Current Output
  • RF Immunity
  • Short Circuit Protection
  • Power-on Value
  • Safe Value
  • 4 kV ESD Protection
  • Wide Operating Temperature Range: -25 to +75°C

Analog Output

Channels: 8
Current Output Wiring: Source
Range: 0 ~ +5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA
Resolution: 16-bit
Accuracy: ±0.02% of FSR
Zero Drift: ±0.2 μV/°C
Span Drift: ±25 ppm/°C
DA Output Response Time: 10 ms per channel
Programmable Output Slope:

  • Voltage: 0.0625 ~ 512 V/Second
  • Current: 0.125 ~ 1024 mA/Second

Output Capacity: 1000 Ω
Open Wire Detection: Yes, +4 ~ +20 mA
Short Circuit Protection: Yes
Power-on Value: Yes
Safe Value: Yes

External Power Requirements

Reverse Polarity Protection: Yes
Powered from Terminal Block: Yes, 15 ~ 30 VDC
Consumption: 7 W

Communication

Interface: RS-485
Format: N, 8, 1
Baud Rate: 1200 ~ 115200 bps
Protocol: DCON
Dual Watchdog: Yes, Module (1.6 Seconds), Communication (Programmable)

LED Display

System LED Indictors: Yes, 1 as Power
I/O LED Indicators: 16 LEDs as Analog Output Fault Indications

Isolation

Intra-module Isolation, Field-to-Logic: 3000 VDC

EMS Protection

ESD (IEC 61000-4-2):

  • ±4 kV Contact for each Terminal
  • ±8 kV Air for Random Point

RS Immunity (IEC 61000-4-3): 3 V/m, 80 MHz ~ 1 GHz

Power

Power Consumption: 0.3 W Max.

Mechanical

Dimensions (L x W x H): 144 mm x 30.3 mm x 134 mm

Environment

Operating Temperature: -25 ~ +75°C
Storage Temperature: -40 ~ +85°C
Humidity: 10 ~ 90% RH, non-condensing