2-ch Channel-to-channel Isolated Analog output Module
The I-87022W is a Sink Type Analog Output Module that includes 2 Analog Output channels, and provides options for configuring power-on and safe values. It also provides a programmable Analog output range (0 ~ +10 V, +4 ~ +20 mA or 0 ~ +20 mA), and each Analog Output can be configured for an individual range. The module provides an RF immunity level matching that defined in the IEC 61000-4-3 standard. Voltage or current output is jumper selectable, and the module also features per-channel open wire detection for +4 ~ +20 mA output, together with ±4 KV ESD protection and 3000 VDC intra-module isolation.
I-87022W-G CR: 2-channel 12-bit Analog Output Module with Channel-to-Channel Isolation (Gray Cover) (RoHS)
- 2-channel Voltage or Current Output
- Individual Channel Configuration
- 3000 VDC Intra-module Isolation
- 3 kV Channel-to-Channel Isolation
- Open Wire Detection for Current Output
- Readback Voltage or Current
- RF Immunity
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- 4 kV ESD Protection
- Wide Operating Temperature Range: -25 to + 75°C
Analog Output
Channels: 2
Current Output Wiring: Sink
Range: 0 ~ +10 V / 0 ~ +20 mA / +4 ~ +20 mA
Resolution: 12-bit
Accuracy: ±0.1% of FSR
Readback Accuracy: ±0.5% of FSR
DA Output Response Time: 10 ms per Channel
Programmable Output Slope: Voltage = 0.0625 ~ 1024.0 V/Second - Current = 0.125 ~ 2048 mA/Second
Current Load Resistance: Internal Power=500 Ω / External Power: 1050 Ω
Voltage Output Capability: 10 V @ 10 mA
Channel-to-Channel Isolation: Yes, 3 kV
Open Wire Detection: Yes, +4 ~ +20 mA
Short Circuit Protection: Yes
Power-on Value: Yes
Safe Value: Yes
Communication
Interface: RS-485
Format: N, 8, 1
Baud Rate: 1200 to 115200 bps
Protocol: DCON
Dual Watchdog: Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator: Yes, 1 as Power/Communication Indicator
I/O LED Indicator: -
Isolation
Intra-module Isolation, Field-to-Logic: 3000 vdc
EMS Protection
ESD (IEC 61000-4-2): ±4 kV Contact for each Terminal / ±8 kV Air for Random Point
RS Immunity (IEC 61000-4-3): 3 V/m, 80 MHz ~ 1 GHz
Power
Power Consumption: 1.8 W Max.
Mechanical
Dimension (L x W x D): 115 mm x 30 mm x 102 mm
Environment
Operating Temp.: -25 to +75°C
Storage Temp.: -40 to +85°C
Humidity: 10 to +95% RH, non-condensing