I-8041PW-G CR
32-ch Isolated Digital output (Sink, NPN, 10~50VDC) Module with Self Protection Includes CA-4002F (DB37 connector Female with plastic cover)
The I-8041W/I-8041PW module offers 32 Digital Output channels, each of which features Photocouple isolation and supports sink-type output using an open collector. The I-8041W/I-8041PW includes 32 LED indicators that can be used to monitor the status of the Digital Output channels. 4 kV ESD protection and 3750 Vrms intra-module isolation is provided as standard. The I-8041W/I-8041PW can be paired with a daughterboard, such as the DN-37-381-A for easy wiring, or the DN-8K32R for relay output.
The I-8041PW integrates over-current, over-voltage and short-circuit functionality. ICP DAS recommends selecting either the "PW" version of the digital output module for industrial use.
I-8041PW-G CR: 32-channel Isolated Self Protected Digital Output Module (Gray Cover) (RoHS)
- 32-channel Open Collector Output
- Sink-tpe Digital Output
- Short circuit protection, Overvoltage Protection and Overload Protection for I-8041PW
- 3750 Vrms Intra-module Isolation
- Each digital channel has its own status LED
- Optional Daughterboards
Digital Output
Channels: 32
Sink/Source (NPN/PNP): Sink
Output Type: Isolated Open Collector
Max. Load Current: 100mA/Channel
Load Voltage: +10 VDC ~ +50 VDC
Overvoltage Protection: 60 VDC
Overload Protection: 1.1A
Short-circuit Protection: Yes
Intra-module Isolation, Field to Logic: 3750 Vrms
LED Display
1 LED as Power Indicator
32 LEDs as Digital Output Indicators
Power
Power Consumption: 1.5 W Max.
Environments
Operating Temo.: -25 ~ +75 °C
Storage Temp.: -30 ~ +85 °C
Humidity: 5 ~ 95%RH, non-condensing
Dimensions
30mm x 85 mm x 114 mm (D x L x H)