Benvenuti sulla nostra nuova piattaforma ICP DAS
Che sostituisce industrialtech.it

HRT-710 CR ICP DAS Gateways

HRT-710 CR ICP DAS

HRT-710 CR

Modbus RTU/ASCII to HART Gateway (RoHS)

Quantity:

Price

€ 357,37

(VAT excluded)

€ 435,99(VAT included)

Prezzo di 1 pz. iva (22%) inclusa: € 435,99

Availability: 15 business days

SKU: 92929

Model: HRT-710 CR

Need Help?


features and benefits

The HRT-710 Gateway is specially designed for the master device of HART protocol.
It allows the Modbus master to access the HART devices.
These HART devices may be a transmitter, an actuator and so forth.
In addition, we also provide the software utility, HG_Tool, for module configuration and HART device diagnosis.
By using these modules, users can integrate their HART devices into Modbus network easily and quickly. HRT-710, a HART master to Modbus slave gateway, is applied to integrate the information from these HART flow meters into the customer's HMI system.
Through the HRT-710, all of the HART flow meters will be regarded as Modbus slave devices and the HMI system can use the built-in Modbus RTU communication to access these HART flow meters easily. More than 250 HART device information needs to be integrated to surveillance center.
In PC side, uses 3 pieces of PCI cards (VXC-148U, for 24 channels RS-485 expansion).
I-2542A and I-2542B (RS-485 to Fiber) are used in every RS-485 channel to extend RS-485 communication distance.
There are about 20 pieces of HRT-710 modules used in every RS-485 channel with the different station ID.
Through the structure, SCADA or HMI system can integrate all HART device information via Modbus protocol easily and quickly.

  • Support HART Short/Long frame
  • Support HART Burst mode
  • Allow two HART Masters
  • Working in point-to-point or multi-drop HART mode
  • Connecting up to 15 HART modules
  • Support Modbus RTU and ASCII format
  • Support Modbus Slave mode
  • Support firmware update via Com Port
  • Support on-line replacement of HART devices
  • Support acquire Long Frame Address automatically
  • Provide LED indicators
  • Built-in Watchdog
  • DIN Rail or Wall Mounting

specifications

COM Ports
PortsRS-232(3 wires) / RS-422 / RS-485
Baud Rate1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
ProtocolModbus RTU / Modbus ASCII
HART
Ports1
Device2-wired or 4-wired HART devices
TopologyPoint to Point or Multi-Drop
DataOnly Digital Data
Frame TypeShort and Long Frame
Burst ModeSupported
Max. HART Device15
Loop Resistor250 Ω (1/4W) by Jumper
IsolationUL1577 Spec.
Protocol2-pin screwed terminal block
Loop PowerNo
Power
Reverse Polarity ProtectionPower reverse polarity protection, Over-voltage brown-out protection
Input RangeUnregulated +10 ~ +30 VDC
Consumption1 W
Mechanical
Dimensions (mm)72 x 35 x 121 (W x L x H) Detail
InstallationDIN-Rail or Wall Mounting (Horizontal)
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80 °C
Humidity10% ~ 90% RH, Non-condensing
Disclaimer